Rated
Output Voltage
The rated output voltage is the output direct voltage ( arithmeticmean
) in case of average load and rated input voltage.
Rated
Power
The maximal permissible output power in W ( watt ) is called
the rated power and is stated as product of rated output direct
voltage, and rated output direct current.
Residual
Ripple (RW )
The proportion of the superimposed power-frequency voltage
to the direct voltage. The value is stated as percentage.
Limiting
Values According to DIN 19240 for 24 V -Direct Current Power
Supplies
Upper
limit of output voltage: |
Peak
value: <30,2 Vs |
in
case of unloaded output and a |
arithmetic
mean: 28,8 V |
mains
overvoltage of + 6% |
( The
arithmetic mean can rise to the peak value, if a capacitor
is used as protective element.)
Lower
limit of output voltage: |
Paek
value: > 18,5 Vs |
in
case of rated output current and a |
arithmetic
mean: 20,4 V |
mains
undervoltage of - 10% |
Residual
ripple: < 5 % |
in
case of rated output current |
General
Information
The transformers,
reactors, and direct current power-supplies represented in
this catalogue are produced according to DIN/VDE 0550 - 0551
- 0532 with greatest possible care.
Dynamo sheets according to DIN 46400 or electrical sheets
with magnetic privileged direction are used as core materials.
This catalogue contains our standard- and stock program, considering
the most customary applications. Due to our stock of standard
materials and the possibility to produce boxes and sheet-metal
parts in our factory, we are also able to realize designs
deviating from our standard program.
The high-quality standard of our products is guaranteed by
strict production control and final inspection and testing
of each unit.
All windings are made of copper. The used insulation materials
are chosen in accordance with the insulation class. An increased
insulation resistance is achieved by impregnating the parts
with resin. This measure also produces a corrosion protection,
if the products are used in dry locations.
Reactors
according
to DIN/VDE 0550 |
-2
kVAR - single-phase |
suitable
for the rated power |
-
10 kVAR - three-phase |
according
to DIN/VDE 0532 |
-
2 kVAR - single-phase |
suitable
for the rated power |
-
10 kVAR - three-phase |
Line-and
Commutating Reactors
These reactors are installed between line and converter installations
in order to increase the natural impedance of the line, to
limit the commutation current, and to damp the interference
voltage. A reac- tive voltage drop of 8.8 V/phase in case
of 380 V, resp. 9,25 V/phase in case of 400 V corresponds
to an impedance voltage ( Uk) of 4 %.
Smothing-
and Filter Reactors
Reactors of this type are inserted in the direct current side
of converter installations in order to reduce the ripple,
to damp the harmonic waves, to limit the currents, and to
damp the noise of the driving mechanism.
Magnetic
Energy Content of a Reactorl
W
|
=
0,5 x L x I² (Ws) |
W |
=
energy in watt-seconds (Ws) |
L |
=
inductivity in henry (H) |
I |
=
current in ampere (A) |
Transformers
Main
Transformers and Power Transformers
Transformers for general use with separate windings and a
basic insulation between primary- and secondary winding.
according
to DIN/VDE 0550 |
<
1 kVA - single-phase |
suitable
for the rated power |
<
5 kVA - three-phaseq |
according
to DIN/VDE 0532 |
1
kVA - single-phase |
suitable
for the rated power |
5
kVA - three-phase |
Isolating
Transformers According to DIN/VDE 0551
secure
electrical separation
the protective measure ,,protective separation" is fulfilled
reinforced or double insulation
rated
output voltage: > 50 V
rated
power: up to 25 kVA |
-
single-phase |
up
to 40 kVA |
-
three-phase |
Safety
Isolating Transformers According to DIN/VDE 0551
secure
electrical separation
the protective measure ,,safety extra-low voltage" is
fulfilled reinforced or double insulation
rated
output voltage: = 50 V ( no-load operation )
rated
power: up to 10 kVA - single-phase up to 16 kVA - three-p
rated
power: |
up
to 10 kVA - single-phase |
|
up
to 16 kVA - three-phase |
Control-power
Transformers According to DIN/VDE 0550
Transformers with separate windings and a basic insulation
between primary- and secondary winding. The dimensions of
control-power transformers have to be designed sufficiently
in order to keep the voltage drop within permissible limits
even under unfavourable circumstances. The pickup power of
all contactors switched on simultaneously results in the short-time
rating of the control-power transformer. Additional power
for other loads must be added to the rated power.
Autotransformers
There is an electrically conductive connection between the
primary- and secondary winding. The power is transmitted partially
inductively and partially by current conduction. The smaller
the difference between primary- and secondary voltage, all
the smaller will be the size or the model output.
according to DIN/VDE 0550 < 1 kVA - single-phase
suitable for the rated power < 5 kVA - three-phase
according to DIN/VDE 0532 > 1 kVA - single-phase
suitable for the rated power > 5 kVA - three-phase
Rated
Input Voltage (PRI-voltage)
The rated input voltage is the line voltage (in case of three-phase
lines the phase-to-phase voltage) for which the transformer
is calculated.
Rated Output Voltage (SEC-voltage)
The output load voltage (in case of three-phase transformers
the phase-to-phase voltage) of a transformer in case of rated
input voltage, rated power, and rated frequency is called
rated output voltage.
Rated
Power (P)
The rated power of a transformer is the maximal permissible
output power in VA and is staded as product of rated output
voltage, rated output current, and power factor. In case of
three-phase transformers this product is multiplied by 1,73.
Rated
Frequency (f)
Operating frequency in Hz for which the transformer is designed.
No-load
Voltage (U )
Output voltage of an unloaded transformer in case of rated
input Voltage, and rated frequency.
No-load
Current (I )
The input current of an unloaded transformer in case of rated
input voltage, and rated frequency.
Impedance
Voltage (U )
Voltage value on the input side of a transformer occuring
in case of short-circuited output winding and the rated output
current flowing there. The value is stated as percentage of
the rated input voltage.
Ambient
Temperature
The ambient temperature is the highest temperature which may
surround the transformer under normal circumstances. If the
transformer is built into a box, it is not alloed to go beyond
the permissible ambient temperature, otherwise the load has
to be reduced
Frequenzy
The transformers contained in this catalogue are designed
for 50 / 60 Hz.
Losses, efficiency, and voltage drop are related to the frequency
of 50 Hz.
The rated power changes, if the frequency deviates from 50
/ 60 Hz.
Insulation
Class
This expression
represents the ambient temperature and the insulation class.
e.g.: T 40/B
(In this case "40" means the ambient temperature
of 40°C and "B" represents the insulation class.)
Multi-winding
Transformers and Tappings
The stated powers are valid for one primary and one secondary
voltage. Tappings up to 5 % do not require a larger core power.
Secondary tappings are measured for the current of the highest
voltage step. Several primary voltages, secondary tappings
for full power, and some secundary windings with the necessary
insulations require a larger core power.
Neutral
Point Load
Vector
Group: YNyn0 resp. YNyn6
To avoid
displacements of the neutral point and additional losses,
it is only allowed to load the neutral point with the full
rated current if the neutral conductor of the supply system
is connected with the transformer-neutral point of the supply
side. Does this not come true, only a load of 10% is permissible.
The same is valid for the star-delta economy connection (YNa0).
Vector
Group: Dyn5 and Dyn II
The neutral point can be loaded with the full rated current
in case of these vector groups.
Vector
Group: Yzn5 or Dzn0
The neutral point is also fully loadable. These vector groups
are to recommend, if the load of the phases is unbalanced.
But the additional expense for wirings and connection requires
an extra charge.
Operating
Modes
Continous
operation (DB)
The transformer can operate under rated load as long as you
like. The rated powers stated in the catalogue are valid for
continous operation.
Short-time operation (KB)
The admissible final temperature is not reached because the
load period is so short. In the intervals between the load
periods the temperature falls to the degree of the ambient
temperature.
Intermittent operation (AB)
The operating time (ED) is stated. In the intervals between
the load periods, the temperature does not fall to the degree
of the ambient temperature.
Definition of the operating time (ED)
The proportion of load period to cycle duration in case of
intermittent operation. The cycle duration is composed of
the load period and the interval between the load periods.
Overload
- and Short - circuit Protection
Generally, built-in transformers are not protected against
overload and short-circuit.
Because of the high inrush current, which can be, possibly,
the fiftyfold of the nominal input current, a protection by
means of fuses or automatic ciruit-breakers is only possible
in case of short-circuit but not in case of overload.
A better protection can be achieved by using a circuit-breaker
with a thermomagnetic release (starting circuit-breaker, power
breaker), which can be adjusted to the primary rated current.
As a result of increased winding temperature in case of short-circuit
or overload, another possibility is to insert temperature-controlled
sensors in the windings. In this case an external switching
device turning off (e.g. thermistor protection, thermal cut-outs,
temperature controllers). To use or starting current limiters
is also recommendable.
Overtemperature
The temperature caused by the specific heat capacity of the
transformer under fixed operating conditions is called overtemperature.
The difference between the nominal- resp. Ambient temperature
and the temperature of the insulation class is the highest
permissible overtemperature. The possible overtemperature
has to be reduced because of hot spots and the reduction is
dependent on the insulation class. Therefore, the permissible
overtemperatures in case of an ambient temperature of 40°
C are as fallows:
E
= |
75°
C |
B
= |
80°
C |
F
= |
100°
C |
H
= |
125°
C |
Protection
Class
The stated
protection class specifies the protective measures which secure
a device against inadmissible touch voltage.
Protection
Class I
Protection
Class I characterizes devices, whose touchable metal parts,
which can be energized in case of a fault in the basic insulation,
are connected to the safety earth terminal. The connection
of the safety earth terminal charcterizes the protective measure
"protective earthing".
Protection
Class II (totally insulated)
Protection class II charcterizes devices, whose touchable
metal parts are separated by means of an additional insulation
from other parts, which can be energized in case of a fault
in the basic insulation. They have no earth connection.
Open transformers (IP 00) designated for the installation
in a device are only prepared for a special protection class.
Transformers prepared for protection class II can also be
used in devices of protection class I.
Protection Type (DIN 40050/IEC 144)
IP
00 |
Open
frame Without any protection against water and dust |
IP
23 |
protection
against spray water Protection against particles >
12mm dia. |
IP
55 |
protection
against water jets (all directions) Protection against
dust coverage |
Short-circuit Withstand Capability
The transformers are classified with regard to their capability
to withstand short circuit as follows:
Inherently
short-ciruit-proof |
Non-inherently
short-ciruit-proof |
Non-short-circuit-proof |
Inherently
short-circuit-proof transformers have no protective device.
The capability to withstand short circuit is achieved by internal
voltage drop. This can be realized by design, e.g. high-reactance
transformers.
Non-inherently short-circuit-proof transformers have a protective
device which opens or limits the electric circuit in case
of short circuit or overload. Fuses, excess-current circuit-breakers,
thermal cut-outs and PTC thermistors are customary protective
devices.
Non-short-circuit-proof transformers have no built-in protective
device and have to be protected against overload by means
of protective measures within the incoming line or the outgoing
cable.
Temperature
Class of Insulation
Size, loadability and lifetime of a transformer are determined
substantially by the used insulating materials.
According to IEC85 the temperature clsses of insulation are
classified as follows:
E |
=
120° C |
B |
=
130° C |
F |
=
155° C |
H |
=
180° C |
Vector
Group (three-phase transformers)e
The vector
group indicates the winding connections and the ciruit arrangement
of their phase angle to each other. Its symbol consists of
a capital letter for the input voltage, a small letter for
the output voltage, and a code number. In case of brought-out
neutral point "N" resp. "n" is added,
for example YNyn0 - Dyn5 - YNa0.
The following
table represents a range of the most customary vector groups.
Our standard types are designed according to vector group
YNyn0 resp. Dyn5 in case of separate windings and according
to vector group YNa0 in case of autotransformers.
Three
phase transformers
YNyn0 |
primary
= connection with neutral point |
|
N
= neutral point accessible |
|
Secondary
= connection with neutral point |
|
n
= neutral point accessible |
|
|
Dyn5 |
primary
= connecting without neutral point |
|
secondary
= connection with neutral point |
|
n
= neutral point accessible |
Autotransformers
YNa0 |
primary
and secondary = connection with neutral point |
|
n
= neutral point accessible |
|